Abstract
This paper proposes a new method of starting the hybrid power filter for wind power generation systems with soft starter. In the proposed method, an active filter of the hybrid power filter behaves a resistor for the source current under the starting condition. Thus the inrush phenomena of the passive filter are perfectly suppressed. The basic principle of the proposed starting method is discussed, and then confirmed by digital computer simulation using PSCAD/EMTDC. Simulation results demonstrate that the proposed starting method can overcome the inrush currents for the passive filter, building up the dc voltage of the active filter.
Original language | English |
---|---|
Pages (from-to) | 574-575 |
Number of pages | 2 |
Journal | ieej transactions on industry applications |
Volume | 130 |
Issue number | 4 |
DOIs | |
Publication status | Published - 2010 |
Externally published | Yes |
Keywords
- Harmonic currents
- Hybrid power filter
- Induction generator
- Soft start method
- Wind power generation
ASJC Scopus subject areas
- Industrial and Manufacturing Engineering
- Electrical and Electronic Engineering